Frequently Asked Questions (FAQ)
Q1: How many input channels does the module support?
A1: Sixteen isolated analog channels.
Q2: What signal type does it accept?
A2: 4–20 mA current signals from field transmitters.
Q3: Is it isolated from the system?
A3: Yes—provides 1,500 VAC isolation for 1 minute between inputs and the system.
Q4: Does it support HART communication?
A4: Yes—the HART protocol is supported for digital diagnostics.
Q5: Can I configure each channel independently?
A5: Yes—2‑wire or 4‑wire mode is selectable on a per‑channel basis.
Q6: What is the update speed per channel?
A6: Approximately 10 milliseconds per channel.
Q7: What is the typical operating temperature range?
A7: Around –20 °C to +60 °C under normal conditions.
Q8: Does the module need calibration after installation?
A8: No—factory calibrated and ready for use.
Q9: How much power does the module consume?
A9: Roughly 230 mA at 5 V DC or 540 mA at 24 V DC.
Q10: What are its physical dimensions and weight?
A10: Measures approximately 107.5 × 32.8 × 130 mm and weighs 0.30 kg.